ECODRIVE03-FL*-04VRS
Diagnostic Message Descriptions
12-15
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
F296 Number of EcoX Slaves incorrect
In Parameter B014, EMD Configuration the number of EcoX slaves has
to be entered. If the master notices that the number of EcoX slaves does
not correspond with the parameterized value when scanning the slaves,
warning E296 Number of EcoX slaves incorrect is generated.
The EcoX master cyclically scans the EcoX slaves until their number
corresponds with the parameterized number of EcoX slaves. If warning
E296 is activated and you try to set the controller enable signal, error
F296 is generated.
Cause:
1. The EcoX bus has not been correctly wired
2. The EcoX bus has not been parameterized in an EcoX slave
and/or master
3. The EcoX bus is disturbed
4. The supply voltage of the EcoX slaves was cut off
Remedy:
1. Check the wiring of the EcoX bus
2. Check parameterization
3. Check the EcoX bus
4. Check supply voltage of the EMD modules
F297 Error in EcoX Slave
If an error (e. g. F292 Overtemperature in EMD module) occurs in an
EcoX slave, this is communicated to the EcoX master via the EcoX
interface. Error F297 is then generated in the EcoX master.
Cause:
•
An error occurred in an EcoX slave.
Remedy:
•
Remedy the cause of the error in the EcoX slave. Then delete the
error message in the EcoX slave and in the EcoX master.
F386 No ready signal from supply module
Cause:
Input BbN "Power supply ready“ on the drive controller is at 24V, i.e., the
connected power supply is not issuing a ready signal.
Summary of Contents for Rexroth OptiFeed-FS EcoDrive 03 FLP04VRS
Page 18: ...XVI Table of Contents ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P ...
Page 348: ...11 18 Command Communications ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Page 418: ...13 4 Connectors ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Page 470: ...16 4 IDS Accessories ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Page 489: ......