9-38
Parameters
ECODRIVE03-FL*-04VRS
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
2) Byte Output
With this option, it is possible to directly output data memory storage
location as an analog voltage. However, this is only useful if the data
storage structure is known. Since this structure differs from version to
version, this function can only be used by developers. The function is
activated by setting Bit 28 in Parameter B007, Analog Output 2,
Expanded Signal Select. The address of the storage location is defined
in the 24 least significant bits of the expanded signal selection.
31 30 29 282726 252423 2221 2019 1817 1615 1413 1211 10 9 8 7 6 5 4 3 2 1 0
Bit 28 :
Byte output
Bit 0..23
24 Bit address
Fig. 9-19: Definition of B007, Analog Output 2, Expanded Signal Select with
Byte Output
3) Bit Output
With this option, individual bits of the data memory can be represented as
an analog voltage. If the bit in question is set, 10 volts are output at the
analog output. In response to a reset bit, -10 volts are output. The
function is activated by setting Bit 29 and inputting the desired memory
address in Parameter B007, Analog Output 2, Expanded Signal
Select.
31 30 29 282726 252423 2221 2019 1817 1615 1413 1211 10 9 8 7 6 5 4 3 2 1 0
Bit 0..23
24 Bit address
Bit 29 :
Bit output
Fig. 9-20: Definition of B007, Analog Output 2, Expanded Signal Select with
Bit Output
Summary of Contents for Rexroth OptiFeed-FS EcoDrive 03 FLP04VRS
Page 18: ...XVI Table of Contents ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P ...
Page 348: ...11 18 Command Communications ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Page 418: ...13 4 Connectors ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Page 470: ...16 4 IDS Accessories ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Page 489: ......