The calculated
OC_TIME
output reflects the timings when the IED
receives the input currents. Hence, the actual time of the trigger
matches the
OC_TIME
output only if the current inputs remain the
same throughout the duration of the overload. If the input current
changes subsequently, the
OC_TIME
output time also changes
correspondingly.
The output
ELAPSE_TIME
is time elapse after
OC_STR
is TRUE.
The outputs
OC_TIME
and
ELAPSE_TIME
are reported for the monitoring view.
Once the output
OC_STR
is FALSE, the outputs
OC_TIME
and
ELAPSE_TIME
are
reset.
The module can be reset by the input
RESET_OC
. If the input
RESET_OC
is TRUE,
the outputs
OC_OPR
,
OC_TIME
and
ELAPSE_TIME
are reset.
The different ANSI/IEC curve type operating time characteristic depends on the
Curve parameter A
,
Curve parameter B
,
Curve parameter C
,
Curve parameter D
,
Curve parameter E
,
Time multiplier
,
Operating curve type
,
Operate delay time
and
Minimum operate time
settings. Similarly, the reset curve functionality depends on the
Type of reset curve
and
Reset delay time
settings.
In this function block, some of the settings are set in per unit (pu). These per unit values
are relational to the certain base values. The PML630 IED supports alternative base
value groups in the
Base value Sel phase
setting, for example “Phase Grp 1”, “Phase
Grp 2” and “Phase Grp 3”.
The output
INVAL_CRV
is TRUE if the
Operating curve type
setting is selected
"Programmable" and the curve parameter values are invalid, else the output
INVAL_CRV
is FALSE.
For more information on overcurrent start and operate based on
different
Timer characteristics
and relevant inputs, see the PHLPTOC
function of the three-phase non-directional overcurrent protection
PHxPTOC in the 630 series technical manual.
For a detailed description of the definite time characteristics and
current based inverse definite minimum time (IDMT) characteristics,
see the general function block features section in this manual.
The overcurrent settings in PML630 must be coordinated carefully
with the IED of the power source.
The external slow load-shedding trigger is also initiated if the input
EXT_OC_SLST
changes from FALSE to TRUE.
1MRS757256 F
Section 7
Power management functions
PML630/Compact Load-Shedding Solution
223
Technical Manual
Summary of Contents for Relion 630 Series
Page 1: ... RELION 630 SERIES Power Management PML630 Compact Load Shedding Solution Technical Manual ...
Page 2: ......
Page 26: ...20 ...
Page 38: ...32 ...
Page 202: ...196 ...
Page 322: ...316 ...
Page 360: ...354 ...
Page 374: ...368 ...
Page 376: ...370 ...