![ABB Relion 630 Series Technical Manual Download Page 195](http://html.mh-extra.com/html/abb/relion-630-series/relion-630-series_technical-manual_2813195.webp)
4.1.5
Application
The function block can be used for any general analog signal protection, either
underprotection or overprotection. The setting range is wide, allowing various
protection schemes for the function. Thus, the absolute hysteresis can be set to a value
that suits the application.
The temperature protection using the RTD sensors can be done using the function
block. The measured temperature can be fed from the RTD sensor to the function input
that detects too high temperatures in the motor bearings or windings, for example.
When the
ENA_ADD
input is enabled, the threshold value of the internal comparator
is the sum of the
Start value Add
and
Start value
settings. This allows a temporal
increase or decrease of the level detector depending on the sign and value of the
Start
value Add
setting, for example, when the emergency start is activated. If, for example,
Start value
is 100,
Start value Add
is 20 and the
ENA_ADD
input is active, the input
signal needs to rise above 120 before MAPGAPC operates.
4.1.6
Signals
Table 235:
MAPGAPC Input signals
Name
Type
Default
Description
AI_VALUE
REAL
0.0
Analog input value
BLOCK
BOOLEAN
0
Block overall function
BLK_OPR
BOOLEAN
0
Block operate output
BLK_ST
BOOLEAN
0
Block start output
FR_TIMER
BOOLEAN
0
Freeze internal operate timer
ENA_ADD
BOOLEAN
0
Enable start using added start value
Table 236:
MAPGAPC Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operated
START
BOOLEAN
Started signal
4.1.7
Settings
Table 237:
MAPGAPC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Start value
-10000.0 - 10000.0
-
0.1
0.0
Start value
Start value Add
-100.0 - 100.0
-
0.1
0.0
Added value to start value
Operate delay time
0.03 - 200.00
s
0.01
0.03
Operate delay time
1MRS757256 F
Section 4
Protection functions
PML630/Compact Load-Shedding Solution
189