![ABB Relion 630 Series Technical Manual Download Page 246](http://html.mh-extra.com/html/abb/relion-630-series/relion-630-series_technical-manual_2813246.webp)
Table 282:
PRIO_L1_5 bits information
Bits
Bits description
1...5
Sheddable load1 priority
6...10
Sheddable load2 priority
11...15
Sheddable load3 priority
16...20
Sheddable load4 priority
21...25
Sheddable load5 priority
Similarly, the priority for each sheddable load that is sheddable
load6...10 is represented by consecutive five bits of
PRIO_L6_L10
.
The output
B_SET_CHANGE
remains active for 500 ms if one or more basic settings
are changed. After 500 ms, the output
B_SET_CHANGE
is FALSE.
The group output
BB
consists of signals for ten sheddable loads which are provided to
the LSCACLS function.
Table 283:
Group signals for BB
Signal description
Group signal BB
Active power of sheddable load1 to sheddable
load10
L1_POWER to L10_POWER
Shed priority data of sheddable loads 1...5
PRIO_L1_5
Shed priority data of sheddable loads 6...10
PRIO_L6_10
7.5.5
Signals
Table 284:
LDMMXU Input signals
Name
Type
Default
Description
POWER_L1
REAL
0.0
Active power of sheddable load1
CB_POS_L1
INTEGER
1
Circuit breaker position of the sheddable load1
IED_QVAL_L1
BOOLEAN
1
Circuit breaker IED quality status of sheddable
load1
IED_TEST_L1
BOOLEAN
0
IED test mode behaviour of sheddable load1
EXT_INH_L1
BOOLEAN
0
External inhibit of sheddable load1
POWER_L2
REAL
0.0
Active power of sheddable load2
CB_POS_L2
INTEGER
1
Circuit breaker position of sheddable load2
IED_QVAL_L2
BOOLEAN
1
Circuit breaker IED quality status of sheddable
load2
IED_TEST_L2
BOOLEAN
0
IED test mode behaviour of sheddable load2
EXT_INH_L2
BOOLEAN
0
External inhibit of sheddable load2
POWER_L3
REAL
0.0
Active power of sheddable load3
CB_POS_L3
INTEGER
1
Circuit breaker position of sheddable load3
Table continues on next page
Section 7
1MRS757256 F
Power management functions
240
PML630/Compact Load-Shedding Solution
Technical Manual
Summary of Contents for Relion 630 Series
Page 1: ... RELION 630 SERIES Power Management PML630 Compact Load Shedding Solution Technical Manual ...
Page 2: ......
Page 26: ...20 ...
Page 38: ...32 ...
Page 202: ...196 ...
Page 322: ...316 ...
Page 360: ...354 ...
Page 374: ...368 ...
Page 376: ...370 ...