t[s] Reset time (in seconds)
k
set
Time multiplier
I
Measured current
I>
set
Start value
Table 355:
Coefficients for ANSI delayed inverse reset curves
Curve name
D
(1) ANSI Extremely Inverse
29.1
(2) ANSI Very Inverse
21.6
(3) ANSI Normal Inverse
0.46
(4) ANSI Moderately Inverse
4.85
(6) Long Time Extremely Inverse
30
(7) Long Time Very Inverse
13.46
(8) Long Time Inverse
4.6
1MRS757256 F
Section 9
General function block features
PML630/Compact Load-Shedding Solution
345
Technical Manual