The user can define the delayed inverse reset time characteristics with the following
formula using the set
Curve parameter D
.
t s
D
I
I
k
[ ]
=
>
−
⋅
2
1
A060817 V3 EN
(Equation 26)
t[s] Reset time (in seconds)
k
set
Time multiplier
D
set
Curve parameter D
I
Measured current
I>
set
Start value
1MRS757256 F
Section 9
General function block features
PML630/Compact Load-Shedding Solution
353
Technical Manual