Table 238:
MAPGAPC Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Operation Off/On
Operation mode
Over
Under
-
-
Over
Operation mode (1=Over;2=Under)
Table 239:
MAPGAPC Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Absolute hysteresis
0.01 - 100.00
-
0.01
0.10
Absolute hysteresis for operation
Reset delay time
0.00 - 60.00
s
0.01
0.00
Reset delay time
4.1.8
Measured values
Table 240:
MAPGAPC Measured values
Name
Type
Default
Description
AI_VALUE
REAL
0.0
Analog input value
BLOCK
BOOLEAN
0
Block overall function
BLK_OPR
BOOLEAN
0
Block operate output
BLK_ST
BOOLEAN
0
Block start output
FR_TIMER
BOOLEAN
0
Freeze internal operate timer
ENA_ADD
BOOLEAN
0
Enable start using added start value
4.1.9
Monitored data
Table 241:
MAPGAPC Monitored data
Name
Type
Values (Range)
Unit
Description
OPERATE
BOOLEAN
0=FALSE
1=TRUE
-
Operated
START
BOOLEAN
0=FALSE
1=TRUE
-
Started signal
START_DUR
REAL
-
%
Start duration in
percentage of the total
operating time
4.1.10
Technical data
Table 242:
MAPGAPC Technical data
Characteristic
Value
Operate time accuracy
±1.0% of the set value or ±20 ms
Section 4
1MRS757256 F
Protection functions
190
PML630/Compact Load-Shedding Solution
Technical Manual