Table 55:
A3RADR Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Nominal value Ch 21 0.0 - 999999.9
-
0.1
0.0
Nominal value for
analog channel 21
Under trigger Ch 21
Off
On
-
-
Off
Use under level
trigger for analog
channel 21 (on) or
not (off)
Under Trg Lev Ch 21 0 - 200
%
1
50
Under trigger level
for analog channel
21 in % of signal
Over trigger Ch 21
Off
On
-
-
Off
Use over level
trigger for analog
channel 21 (on) or
not (off)
Over Trg Lev Ch 21
0 - 5000
%
1
200
Over trigger level for
analog channel 21 in
% of signal
IEC60870-5-103
Function type Ch 21
0 - 255
-
1
0
Function type for
analog channel 21
(IEC60870-5-103)
Information Num Ch
21
0 - 255
-
1
0
Information number
for analog channel
21
(IEC60870-5-103)
3.14.4
Binary input signals BxRBDR
3.14.4.1
Function block
B1RBDR
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16
IEC09000352-1-en.vsd
IEC09000352 V1 EN
Figure 47:
Function block
1MRS757256 F
Section 3
Basic functions
PML630/Compact Load-Shedding Solution
89
Technical Manual
Summary of Contents for Relion 630 Series
Page 1: ... RELION 630 SERIES Power Management PML630 Compact Load Shedding Solution Technical Manual ...
Page 2: ......
Page 26: ...20 ...
Page 38: ...32 ...
Page 202: ...196 ...
Page 322: ...316 ...
Page 360: ...354 ...
Page 374: ...368 ...
Page 376: ...370 ...