3.14.1.5
Signals
Table 46:
DRRDRE Output signals
Name
Type
Description
DRPOFF
BOOLEAN
Disturbance report function turned off
RECSTART
BOOLEAN
Disturbance recording started
RECMADE
BOOLEAN
Disturbance recording made
CLEARED
BOOLEAN
All disturbances in the disturbance report cleared
MEMUSED
BOOLEAN
More than 80% of memory used
3.14.1.6
Settings
Table 47:
DRRDRE Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
Pre-trigger time
0.05 - 3.00
s
0.01
0.10
Pre-fault recording time
Post-trigger time
0.1 - 10.0
s
0.1
0.5
Post-fault recording time
Recording time limit
0.5 - 8.0
s
0.1
1.0
Fault recording time limit
Post-retrig
Off
On
-
-
Off
Post-fault retrig enabled (On) or not (Off)
Max Num records
10 - 100
-
1
100
Maximum number of stored disturbances
Reference channel
1 - 30
Ch
1
1
Trip value recorder, phasor reference
channel
Operation mode test
Off
On
-
-
Off
Operation mode during test mode
3.14.1.7
Monitored data
Table 48:
DRRDRE Monitored data
Name
Type
Values (Range)
Unit
Description
DRPOFF
BOOLEAN
0=FALSE
1=TRUE
-
Disturbance report
function turned off
RECSTART
BOOLEAN
0=FALSE
1=TRUE
-
Disturbance recording
started
RECMADE
BOOLEAN
0=FALSE
1=TRUE
-
Disturbance recording
made
CLEARED
BOOLEAN
0=FALSE
1=TRUE
-
All disturbances in the
disturbance report
cleared
MEMUSED
BOOLEAN
0=FALSE
1=TRUE
-
More than 80% of
memory used
Memory used
INTEGER
-
%
Memory usage (0-100%)
Fault number
INTEGER
-
-
Disturbance fault number
1MRS757256 F
Section 3
Basic functions
PML630/Compact Load-Shedding Solution