![ABB Relion 630 Series Technical Manual Download Page 193](http://html.mh-extra.com/html/abb/relion-630-series/relion-630-series_technical-manual_2813193.webp)
Section 4
Protection functions
4.1
Multipurpose analog protection MAPGAPC
4.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Multipurpose analog protection
MAPGAPC
MAP
MAP
4.1.2
Function block
GUID-75500106-5F41-4834-9D02-40282D4C7221 V1 EN
Figure 122:
Function block
4.1.3
Functionality
The multipurpose analog protection function MAPGAPC is used as a general
protection with many possible application areas as it has flexible measuring and
setting facilities. The function can be used as an underprotection or overprotection
with a settable absolute hysteresis limit. The function operates with the definite time
(DT) characteristics.
The function contains a blocking functionality. It is possible to block function outputs,
the definite timer or the function itself, if desired.
4.1.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The
corresponding parameter values are "On" and "Off".
The operation of the multipurpose analog protection function can be described using
a module diagram. All the modules in the diagram are explained in the next sections.
1MRS757256 F
Section 4
Protection functions
PML630/Compact Load-Shedding Solution
187
Technical Manual