Trip Value Rec
Event List
Event Recorder
Indications
Disturbance
Recorder
AxRADR
BxRBDR
Disturbance Report
Binary signals
Analog signals
RDRE
IEC09000136-2-en.vsdx
IEC09000136 V2 EN
Figure 41:
Disturbance report functions and related function blocks
The whole disturbance report can contain information for a number of recordings,
each with the data coming from all the parts mentioned above. The event list function
is working continuously, independent of disturbance triggering, recording time, and
so on. All information in the disturbance report is stored in non-volatile flash
memories. This implies that no information is lost in case of loss of auxiliary power.
Each report gets an identification number in the interval from 0-999.
en05000161.vsd
Disturbance report
Record no. N
Record no. N+1
Record no. N+100
General dist.
information
Indications
Trip
values
Event
recordings
Disturbance
recording
Event list
IEC05000161 V1 EN
Figure 42:
Disturbance report structure
Up to 100 disturbance reports can be stored. If a new disturbance is to be recorded
when the memory is full, the oldest disturbance report is overwritten by the new one.
The total recording capacity for the disturbance recorder is depending of sampling
Section 3
1MRS757256 F
Basic functions
78
PML630/Compact Load-Shedding Solution
Technical Manual