5.1.9
Monitored Data
Table 248:
SPVNZBAT Monitored data
Name
Type
Values (Range)
Unit
Description
U_BATT
REAL
-
kV
Service value of the
battery terminal voltage
AL_ULOW
BOOLEAN
0=FALSE
1=TRUE
-
Alarm when voltage has
been below lower limit for
a set time
AL_UHIGH
BOOLEAN
0=FALSE
1=TRUE
-
Alarm when voltage has
exceeded higher limit for
a set time
ST_ULOW
BOOLEAN
0=FALSE
1=TRUE
-
Start signal when battery
voltage drops below
lower limit
ST_UHIGH
BOOLEAN
0=FALSE
1=TRUE
-
Start signal when battery
voltage exceeds upper
limit
5.1.10
Technical data
Table 249:
SPVNZBAT Technical data
Characteristic
Value
Operation accuracy
±1.0% of the set value
Operate time accuracy
±1.0% of the set value or ±40 ms
1MRS757256 F
Section 5
Supervision functions
PML630/Compact Load-Shedding Solution
195
Technical Manual