9.2.2
Reset in inverse-time modes
The user can select the reset characteristics by using the
Type of reset curve
setting.
Table 354:
Values for reset mode
Setting name
Possible values
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
Immediate reset
If the
Type of reset curve
setting in a drop-off case is selected as "Immediate", the
inverse timer resets immediately.
Definite time reset
The definite type of reset in the inverse-time mode can be achieved by setting the
Type
of reset curve
parameter to “Def time reset”. As a result, the operate inverse-time
counter is frozen for the time determined with the
Reset delay time
setting after the
current drops below the set
Start value
, including hysteresis.The integral sum of the
inverse-time counter is reset, if another start does not occur during the reset delay.
If the
Type of reset curve
setting is selected as “Def time reset”, the
current level has no influence on the reset characteristic.
Inverse reset
Inverse reset curves are available only for ANSI and user-
programmable curves. If you use other curve types, immediate reset
occurs.
Standard delayed inverse reset
The reset characteristic required in ANSI (IEEE) inverse-time modes is provided by
setting the
Type of reset curve
parameter to “Inverse reset”. In this mode, the time
delay for reset is given with the following formula using the coefficient D, which has
its values defined in the table below.
t s
D
I
I
k
[ ]
=
>
−
⋅
2
1
A060817 V3 EN
(Equation 25)
Section 9
1MRS757256 F
General function block features
344
PML630/Compact Load-Shedding Solution
Technical Manual