Bus bar
Bus bar
Sending end circuit
breaker
GUID-A6CA8B40-4791-4E4E-93B7-1C73D8B82943 V2 EN
Figure 141:
Bus coupler configuration
Bus bar
Bus bar
Sending end circuit
breaker
Receiving end circuit
breaker
GUID-96DFC4D7-7235-411B-A843-15A2922DE558 V2 EN
Figure 142:
Tie circuit breaker configuration
This module converts the units of
SND_CB_POWER
(sending-end circuit breaker
power) and
RCV_CB_POWER
(receiving-end circuit breaker power) inputs in kW
based on the
Send Pow convention
and
Rcv Pow convention
settings as shown in
Table 290:
Calculation of sending/receiving-end circuit breaker output
Setting
Values
Calculated sending-end CB
power/receiving-end CB power
Send Pow convention
Positive W
SND_CB_POWER × [0.001]
Negative W
SND_CB_POWER × [-0.001]
Positive kW
SND_CB_POWER × [1]
Negative kW
SND_CB_POWER × [-1]
Positive MW
SND_CB_POWER × [1000]
Negative MW
SND_CB_POWER × [-1000]
Rcv Pow convention
Positive W
RCV_CB_POWER × [0.001]
Negative W
RCV_CB_POWER × [-0.001]
Positive kW
RCV_CB_POWER × [1]
Negative kW
RCV_CB_POWER × [-1]
Positive MW
RCV_CB_POWER × [1000]
Negative MW
RCV_CB_POWER × [-1000]
If the
CB configuration
setting is “Bus coupler”, the network circuit breaker power is
same as the calculated sending-end circuit breaker power.
Section 7
1MRS757256 F
Power management functions
250
PML630/Compact Load-Shedding Solution
Technical Manual