![ABB Relion 630 Series Technical Manual Download Page 370](http://html.mh-extra.com/html/abb/relion-630-series/relion-630-series_technical-manual_2813370.webp)
Table 371:
Degree of protection of flush-mounted device
Description
Value
Front side
IP 40
Rear side, connection terminals
IP 20
Table 372:
Degree of protection of the LHMI
Description
Value
Front and side
IP 42
Table 373:
Environmental conditions
Description
Value
Operating temperature range
-25...+55ºC (continuous)
Short-time service temperature range
-40...+85ºC (<16 h)
Note: Degradation in MTBF and HMI performance
outside the temperature range of -25...+55ºC
Relative humidity
<93%, non-condensing
Atmospheric pressure
86...106 kPa
Altitude
up to 2000 m
Transport and storage temperature range
-40...+85ºC
Table 374:
Environmental tests
Description
Type test value
Reference
Dry heat test (humidity <50%)
•
96 h at +55ºC
•
16 h at +85ºC
IEC 60068-2-2
Cold test
•
96 h at -25ºC
•
16 h at -40ºC
IEC 60068-2-1
Damp heat test, cyclic
•
6 cycles at +25…55°C, Rh
>93%
IEC 60068-2-30
Storage test
•
96 h at -40ºC
•
96 h at +85ºC
IEC 60068-2-1
IEC 60068-2-2
Section 11
1MRS757256 F
Technical data
364
PML630/Compact Load-Shedding Solution
Technical Manual
Summary of Contents for Relion 630 Series
Page 1: ... RELION 630 SERIES Power Management PML630 Compact Load Shedding Solution Technical Manual ...
Page 2: ......
Page 26: ...20 ...
Page 38: ...32 ...
Page 202: ...196 ...
Page 322: ...316 ...
Page 360: ...354 ...
Page 374: ...368 ...
Page 376: ...370 ...