3.32.1.12
Equality check for integer signals EQI
Function block
GUID-1E4DCAB8-7969-4E57-A65C-A26406C58649 V1 EN
Figure 86:
Function block
Functionality
The EQI function compares the integer inputs
INT_IN1
and
INT_IN2
and activates
the binary output
OUTPUT
, if
INT_IN1
is equal to
INT_IN2
.
If
INT_IN1
=
INT_IN2
,
OUTPUT
= 1, else
OUTPUT
= 0.
Logic function blocks do not have the hysteresis feature. Oscillating
outputs should be avoided when comparing analog signals that have
very closely varying values.
Signals
Table 148:
EQI Input signals
Name
Type
Default
Description
INT_IN1
INTEGER
0
Integer input 1
INT_IN2
INTEGER
0
Integer input 2
Table 149:
EQI Output signals
Name
Type
Description
OUTPUT
BOOLEAN
Binary output
3.32.1.13
Greater than check for real signals GTR
Function block
GUID-C815667D-B570-4DCD-9E85-359853EBC0FA V1 EN
Figure 87:
Function block
Functionality
The function compares the real inputs
REAL_IN1
and
REAL_IN2
and activates the
binary output
OUTPUT
, if
REAL_IN1
is greater than
REAL_IN2
.
1MRS757256 F
Section 3
Basic functions
PML630/Compact Load-Shedding Solution
153
Technical Manual