3.8.3
Signal matrix for analog inputs SMAI_20_2
SMAI_20_2
BLOCK
REVROT
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
AI3P
AI1
AI2
AI3
AI4
AIN
IEC09000138-2-en.vsd
IEC09000138 V2 EN
Figure 32:
SMAI_20_2 to SMAI_20_12 function block
Note that input and output signals on SMAI_20_2 to SMAI_20_12 are
the same except for input signals GRPxL1 to GRPxN where x is equal
to instance number (2 to 12).
3.8.3.1
Signals
Table 28:
SMAI_20_2 Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block group 2
REVROT
BOOLEAN
0
Reverse rotation group 2
GRP2L1
STRING
-
First analog input used for phase L1 or L1-L2
quantity
GRP2L2
STRING
-
Second analog input used for phase L2 or L2-L3
quantity
GRP2L3
STRING
-
Third analog input used for phase L3 or L3-L1
quantity
GRP2N
STRING
-
Fourth analog input used for residual or neutral
quantity
Table 29:
SMAI_20_2 Output signals
Name
Type
Description
AI3P
GROUP SIGNAL
Grouped three phase signal containing data from
inputs 1-4
AI1
GROUP SIGNAL
Quantity connected to the first analog input
AI2
GROUP SIGNAL
Quantity connected to the second analog input
AI3
GROUP SIGNAL
Quantity connected to the third analog input
AI4
GROUP SIGNAL
Quantity connected to the fourth analog input
AIN
GROUP SIGNAL
Calculated residual quantity if inputs 1-3 are
connected
Section 3
1MRS757256 F
Basic functions
60
PML630/Compact Load-Shedding Solution
Technical Manual
Summary of Contents for Relion 630 Series
Page 1: ... RELION 630 SERIES Power Management PML630 Compact Load Shedding Solution Technical Manual ...
Page 2: ......
Page 26: ...20 ...
Page 38: ...32 ...
Page 202: ...196 ...
Page 322: ...316 ...
Page 360: ...354 ...
Page 374: ...368 ...
Page 376: ...370 ...