3.23
GOOSE function block to receive a double point
GOOSEDPRCV
3.23.1
Function block
IEC10000249-1-en.vsd
GOOSEDPRCV
BLOCK
^DPOUT
DATAVALID
COMMVALID
TEST
IEC10000249 V1 EN
Figure 65:
Function block
3.23.2
Functionality
GOOSEDPRCV is used to receive a double point value using IEC61850 protocol via
GOOSE.
3.23.3
Operation principle
The DATAVALID output is HIGH if the incoming message is with valid data.
The COMMVALID output becomes LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in Signal Matrix by
means of a cross to receive the double point values.
The implementation for IEC 61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD, the DATAVALID
output is HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA, the
DATAVALID output is LOW.
3.23.4
Signals
Table 91:
GOOSEDPRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
Section 3
1MRS757256 F
Basic functions
126
PML630/Compact Load-Shedding Solution
Technical Manual