![ABB Relion 630 Series Technical Manual Download Page 318](http://html.mh-extra.com/html/abb/relion-630-series/relion-630-series_technical-manual_2813318.webp)
7.11.2
Function block
PPLSGGIO
LS_DATA_ER
PEER_CB_STS
PEER_DATA_ER
PEER_SRC_BLK
PEER_SN_BLK
PPLS
NW_PPLS
PEER_SR_STS
PEER_MS_STS
GUID-44A61373-A7B1-43FE-988F-A7DCEA69715C V1 EN
Figure 162:
Function block
7.11.3
Functionality
PPLSGGIO is the output interface for the load-shedding data for an adjacent electrical
area connected with the power source. The load-shedding information is converted
into weighted integer data. This function also provides outputs for the load-shedding
information received from the corresponding connected electrical area.
7.11.4
Operation principle
The operation of PPLSGGIO can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
PPLS
PEER_MUST_LS
General
logic
PEER_SP_RSV
LS_DATA
LS_DATA_ER
PEER_MS_STS
PEER_SRC_BLK
PEER_SN_BLK
PEER_DATA_ER
NW_PPLS
PEER_CB_STS
PEER_SR_STS
GUID-20810C87-7915-4691-B9DD-5BE26E2B4BD4 V1 EN
Figure 163:
Functional module diagram
PPLSGGIO receives the different load-shedding data of the subnetwork from
LSCACLS through the group input
PPLS
.
PPLSGGIO receives the circuit breaker information for external connection and load-
shedding data of the connected adjacent electrical area from NPMMXU function
through the group input
NW_PPLS
.
Section 7
1MRS757256 F
Power management functions
312
PML630/Compact Load-Shedding Solution
Technical Manual