3.25
GOOSE function block to receive a measurand value
GOOSEMVRCV
3.25.1
Function block
IEC10000251-1-en.vsd
GOOSEMVRCV
BLOCK
^MVOUT
DATAVALID
COMMVALID
TEST
IEC10000251 V1 EN
Figure 67:
Function block
3.25.2
Functionality
GOOSEMVRCV is used to receive measured value using IEC61850 protocol via
GOOSE.
3.25.3
Operation principle
The DATAVALID output is HIGH if the incoming message is with valid data.
The COMMVALID output becomes LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in Signal Matrix by
means of a cross to receive the float values.
The implementation for IEC 61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD, the DATAVALID
output is HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA, the
DATAVALID output is LOW.
3.25.4
Signals
Table 97:
GOOSEMVRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function