3.2.3.5
Settings
Table 12:
LEDGEN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
tRestart
0.0 - 100.0
s
0.1
0.0
Defines the disturbance length
tMax
0.0 - 100.0
s
0.1
0.0
Maximum time for the definition of a
disturbance
Table 13:
GRP1_LED1 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
SequenceType
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
-
-
Follow-S
Sequence type for LED 1, local HMI alarm
group 1
LabelOff
0 - 18
-
1
G1L01_OFF
Label string shown when LED 1, alarm
group 1 is off
LabelRed
0 - 18
-
1
G1L01_RED
Label string shown when LED 1, alarm
group 1 is red
LabelYellow
0 - 18
-
1
G1L01_YELLOW
Label string shown when LED 1, alarm
group 1 is yellow
LabelGreen
0 - 18
-
1
G1L01_GREEN
Label string shown when LED 1, alarm
group 1 is green
3.2.4
Display part for HMI function keys control module
3.2.4.1
Function block
FNKEYMD1
^LEDCTL1
^FKEYOUT1
IEC09000327 V1 EN
Figure 25:
Function block
3.2.4.2
Functionality
LHMI has five function buttons, directly to the left of the display, that can be
configured either as menu shortcut or control buttons. Each button has an indication
LED that can be configured in the application configuration.
When used as a menu shortcut, a function button provides a fast way to navigate
between default nodes in the menu tree. When used as a control, the button can control
a binary signal.
1MRS757256 F
Section 3
Basic functions
PML630/Compact Load-Shedding Solution