Signals
Table 189:
RSMEMORYQT Input signals
Name
Type
Default
Description
SET
BOOLEAN
0
Input signal to set
RESET
BOOLEAN
0
Input signal to reset
Table 190:
RSMEMORYQT Output signals
Name
Type
Description
OUT
BOOLEAN
Output signal
NOUT
BOOLEAN
Inverted output signal
Settings
Table 191:
RSMEMORYQT Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Memory
Off
On
-
-
On
Operating mode of the memory function
3.32.2.9
INVALIDQT function block
Function block
INVALIDQT
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
VALID
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
OUTPUT9
OUTPUT10
OUTPUT11
OUTPUT12
OUTPUT13
OUTPUT14
OUTPUT15
OUTPUT16
IEC09000305-1-en.vsd
IEC09000305 V1 EN
Figure 106:
Function block
Functionality
INVALIDQT is a function which sets quality invalid of outputs according to a
VALID
input.
Section 3
1MRS757256 F
Basic functions
168
PML630/Compact Load-Shedding Solution
Technical Manual
Summary of Contents for Relion 630 Series
Page 1: ... RELION 630 SERIES Power Management PML630 Compact Load Shedding Solution Technical Manual ...