10.2
Inputs
10.2.1
Measuring inputs
Each terminal for CTs/VTs is dimensioned for one wire of 0.5...6.0 mm
2
or for two
wires of maximum 2.5 mm
2
.
Table 356:
PML630 modules
Terminal
AIMA01A
1KHL178083R0008
AIMA05A
1KHL178083R0013
X101-1, 2
CT
CT
X101-3, 4
CT
CT
X101-5, 6
CT
CT
X101-7, 8
CT
CT
X101-9, 10
None
CT
X102-1, 2
VT
CT
X102-3, 4
VT
CT
X102-5, 6
VT
CT
X102-7, 8
VT
VT
X102-9, 10
VT
VT
10.2.2
Auxiliary supply voltage input
The auxiliary voltage of the IED is connected to terminals X430-1 and X430-2/3 or
X410-1 and X410-2/3. The terminals used depend on the power supply and the IED
case size.
The permitted auxiliary voltage range of the IED is marked on the device label on the
side of the IED.
Table 357:
Auxiliary voltage supply of 110...250 V DC or 100...240 V AC
Case
Terminal
Description
4U half 19”
X430-1
- Input
X430-3
+ Input
Table 358:
Auxiliary voltage supply of 48-125 V DC
Case
Terminal
Description
4U half 19”
X430-1
- Input
X430-2
+ Input
Section 10
1MRS757256 F
Device's physical connections
356
PML630/Compact Load-Shedding Solution
Technical Manual
Summary of Contents for Relion 630 Series
Page 1: ... RELION 630 SERIES Power Management PML630 Compact Load Shedding Solution Technical Manual ...
Page 2: ......
Page 26: ...20 ...
Page 38: ...32 ...
Page 202: ...196 ...
Page 322: ...316 ...
Page 360: ...354 ...
Page 374: ...368 ...
Page 376: ...370 ...