Name
Type
Values (Range)
Unit
Description
I_RANGE_B
INTEGER
0=Normal
1=High
2=Low
3=High-High
4=Low-Low
-
Phase B amplitude range
I_INST_C
REAL
-
A
Phase C amplitude,
magnitude of
instantaneous value
I_DB_C
REAL
-
A
Phase C amplitude,
magnitude of reported
value
I_ANGL_C
REAL
-
deg
Phase C angle,
instantaneous value
I_RANGE_C
INTEGER
0=Normal
1=High
2=Low
3=High-High
4=Low-Low
-
Phase C amplitude range
6.1.6
Technical data
Table 255:
CMMXU Technical data
Characteristic
Value
Operation accuracy
At the frequency f = f
n
±0.5% or ±0.002 × I
n
(at currents in the range of 0.01...4.00 × I
n
)
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
RMS: No suppression
Section 6
1MRS757256 F
Measurement functions
200
PML630/Compact Load-Shedding Solution
Technical Manual