![ABB Relion 630 Series Technical Manual Download Page 289](http://html.mh-extra.com/html/abb/relion-630-series/relion-630-series_technical-manual_2813289.webp)
The module receives the fast load-shed trigger signals
SRC_FLS_TRG
from the
NPMMXU function and
FLS_TRG_CB
ij
from the respective NCBDCSWI functions.
shows fast load-shed trigger signals for different subnetworks for various
conditions.
OR
EXT_LS_TRG
SRC_FLS_TRG
0
1
FLS_TRG_CB
12
FLS_TRG_CB
56
AND
LS_BLOCK1
AND
AND
LS_BLOCK2
LS_BLOCK3
AND
LS_BLOCK4
FLS_TRG_SNW1
FLS_TRG_SNW2
FLS_TRG_SNW3
FLS_TRG_SNW4
GUID-A97495F6-B1A1-4FCF-BAD7-D6B68AE128EB V1 EN
Figure 153:
Calculation of fast load-shed trigger signal for subnetworks
The module counts the number of times the fast load-shedding trigger signal is
generated and the
FLS_COUNTER
(fast load-shedding counter) output provides the
count. The
FLS_COUNTER
output can be reset through the
FLS_CNT_RST
(fast
load-shedding counter reset) input. The
FLS_COUNTER
output is provided in the
monitoring view.
The module receives the slow load-shed trigger signals,
SLS_TRG_BB1...SLS_TRG_BB4
, for busbar 1...4 from NPMMXU function. If
any of the busbar slow load-shed trigger signal is active, slow load-shed action is
initiated in corresponding subnetwork.
shows slow load-shed trigger signals for different subnetworks for various
conditions.
1MRS757256 F
Section 7
Power management functions
PML630/Compact Load-Shedding Solution
283
Technical Manual
Summary of Contents for Relion 630 Series