Input position (Value)
Signal quality
Output OPENPOS
Output CLOSEPOS
0 (Breaker
intermediate)
Good
0
0
1 (Breaker open)
Good
1
0
2 (Breaker closed)
Good
0
1
3 (Breaker faulty)
Good
0
0
Any
Invalid
0
0
Any
Oscillatory
0
0
8.1.5
Signals
Table 352:
POS_EVAL Input signals
Name
Type
Default
Description
POSITION
INTEGER
0
Position status including quality
Table 353:
POS_EVAL Output signals
Name
Type
Description
OPENPOS
BOOLEAN
Open position
CLOSEPOS
BOOLEAN
Close position
8.1.6
Settings
The function does not have any parameters available in LHMI or PCM600.
Section 8
1MRS757256 F
Control functions
318