3.14.4.2
Signals
Input signal tables for B1RBDR - B4RBDR are all similar except for the INPUT
number.
•
B1RBDR, INPUT1 - INPUT16
•
B2RBDR, INPUT17 - INPUT32
•
B3RBDR, INPUT33 - INPUT48
•
B4RBDR, INPUT49 - INPUT64
Table 56:
B1RBDR input signals
Name
Type
Default
Description
INPUT1
BOOLEAN
0
Binary channel 1
Input settings are the same for each channel. The channel numbers are
shown after the parameter name in LHMI and PCM600.
3.14.4.3
Settings
Setting tables for B1RBDR - B4RBDR are all similar except for the binary channel
numbers.
•
B1RBDR, channel1 - channel16
•
B2RBDR, channel17 - channel32
•
B3RBDR, channel33 - channel48
•
B4RBDR, channel49 - channel64
Table 57:
B1RBDR Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Trigger operation 1
Off
On
-
-
Off
Trigger operation On/Off
Set LED 1
Off
Start
Trip
Start and Trip
-
-
Off
Set LED on HMI for binary channel 1