Name
Type
Description
OUTPUT14
BOOLEAN
Indication output 14
OUTPUT15
BOOLEAN
Indication output 15
OUTPUT16
BOOLEAN
Indication output 16
Settings
The function does not have any parameters available in LHMI or PCM600.
3.32.3
Application
A set of standard logic blocks, like AND or OR, and timers are available for adapting
the IED configuration to the specific application needs. Additional logic blocks that
have the capability to propagate timestamp and quality beside the normal logical
function are also available. Those blocks have a designation including the letters QT,
for example, ANDQT or ORQT.
3.32.4
Technical data
Table 194:
Configurable logic blocks
Logic block
Quantity with cycle time
Range or
value
Accuracy
fast
medium
normal
AND
60
60
160
-
-
B16I
5
5
-
-
-
GATE
10
10
20
-
-
IB16A
5
5
-
-
-
INVERTER
30
30
80
-
-
ITOR
10
10
10
-
-
LOOPDELAY
10
10
20
-
-
MINMAXR
5
10
5
-
-
OR
60
60
160
-
-
PULSETIMER
10
10
20
(0.000–
90000.000) s
± 0.5% ± 25 ms
RSMEMORY
10
10
20
-
-
RTOI
10
10
10
SRMEMORY
10
10
20
-
-
SWITCHI
10
10
10
-
-
SWITCHR
10
10
10
-
-
TIMERSET
10
10
20
(0.000–
90000.000) s
± 0.5% ± 25 ms
XOR
10
10
20
-
-
Section 3
1MRS757256 F
Basic functions
170
PML630/Compact Load-Shedding Solution
Technical Manual