If
REAL_IN1
>
REAL_IN2
,
OUTPUT
= 1, else
OUTPUT
= 0.
Logic function blocks do not have the hysteresis feature. Oscillating
outputs should be avoided when comparing analog signals that have
very closely varying values.
Signals
Table 150:
GTR Input signals
Name
Type
Default
Description
REAL_IN1
REAL
0.0
Real input 1
REAL_IN2
REAL
0.0
Real input 2
Table 151:
GTR Output signals
Name
Type
Description
OUTPUT
BOOLEAN
Binary output
3.32.1.14
Greater than check for integer signals GTI
Function block
GUID-618CF33F-802B-47F4-9AB2-5CE2AA4B3131 V1 EN
Figure 88:
Function block
Functionality
The function compares the integer inputs
INT_IN1
and
INT_IN2
and activates the
binary output
OUTPUT
, if
INT_IN1
is greater than
INT_IN2
.
If
INT_IN1
>
INT_IN2
,
OUTPUT
= 1, else
OUTPUT
= 0.
Logic function blocks do not have the hysteresis feature. Oscillating
outputs should be avoided when comparing analog signals that have
very closely varying values.
Signals
Table 152:
GTI Input signals
Name
Type
Default
Description
INT_IN1
INTEGER
0
Integer input 1
INT_IN2
INTEGER
0
Integer input 2
Section 3
1MRS757256 F
Basic functions
154
PML630/Compact Load-Shedding Solution
Technical Manual