Table 195:
Configurable logic Q/T
Logic block
Quantity with cycle time
Range or value
Accuracy
medium
normal
ANDQT
20
100
-
-
INVALIDQT
6
6
-
-
INVERTERQT
20
100
-
-
ORQT
20
100
-
-
PULSETIMERQT
10
30
(0.000-90000.0
00) s
± 0.5% ± 25 ms
RSMEMORYQT
10
30
-
-
SRMEMORYQT
10
30
-
-
TIMERSETQT
10
30
(0.000-90000.0
00) s
± 0.5% ± 25 ms
XORQT
10
30
-
-
3.33
Boolean 16 to integer conversion B16I
3.33.1
Function block
B16I
BLOCK
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16
OUT
IEC09000035-1-en.vsd
IEC09000035 V1 EN
Figure 107:
Function block
3.33.2
Functionality
Boolean 16 to integer conversion function (B16I) is used to transform a set of 16
binary (logical) signals into an integer.
3.33.3
Operation principle
Boolean 16 to integer conversion function (B16I) is used to transform a set of 16
binary (logical) signals into an integer. The BLOCK input freezes the output at the last
value.
1MRS757256 F
Section 3
Basic functions
PML630/Compact Load-Shedding Solution
171
Technical Manual