Section 12
Device and functionality tests
Table 375:
Electromagnetic compatibility tests
Description
Type test value
Reference
100 kHz and 1 MHz burst
disturbance test
IEC 61000-4-18, level 3
IEC 60255-22-1
•
Common mode
2.5 kV
•
Differential mode
1.0 kV
3 MHz, 10 MHz and 30 MHz
burst disturbance test
IEC 61000-4-18
IEC 60255-22-1, class III
•
Common mode
2.5 kV
Electrostatic discharge test
IEC 61000-4-2, level 4
IEC 60255-22-2
IEEE C37.90.3.2001
•
Contact discharge
8 kV
•
Air discharge
15 kV
Radio frequency interference
tests
•
Conducted, common
mode
10 V (rms), f=150 kHz...80 MHz
IEC 61000-4-6 , level 3
IEC 60255-22-6
•
Radiated, pulse-
modulated
10 V/m (rms), f=900 MHz
ENV 50204
IEC 60255-22-3
•
Radiated, amplitude-
modulated
10 V/m (rms), f=80...2700 MHz
IEC 61000-4-3, level 3
IEC 60255-22-3
Fast transient disturbance tests
IEC 61000-4-4
IEC 60255-22-4, class A
•
All ports
4 kV
Surge immunity test
IEC 61000-4-5, level 3/2
IEC 60255-22-5
•
Communication
1 kV line-to-earth
•
Binary inputs, voltage
inputs
2 kV line-to-earth
1 kV line-to-line
•
Other ports
4 kV line-to-earth, 2 kV line-to-
line
Power frequency (50 Hz)
magnetic field
IEC 61000-4-8
Table continues on next page
1MRS757256 F
Section 12
Device and functionality tests
PML630/Compact Load-Shedding Solution
365
Technical Manual