1.
Set
WEI
to
Echo & Trip
This echoes CR signal as well as trip locally.
2.
Set
tPickUpWEI
to
0.01 s
Shortest duration of CR signal.
3.
Set
UPP<
to lower than the lowest possible phase-to-phase voltage at non-faulted
operation. The setting is done in % of rated phase-to-phase voltage.
Default setting is
70 %
.
4.
Set
UPN<
to lower than the lowest possible phase-to-ground voltage at non-faulted
operation. The setting is done in % of rated phase-to-ground voltage.
Default setting is
70 %
.
3.1.13
Calculating settings for breaker failure protection 3-phase
activation and output CCRBRF (50BF)
Breaker failure protection 3-phase activation and output (CCRBRF , 50BF) can use either
contact function in the circuit breaker or current measurement to detect correct breaker
function. For line protections the most suitable way is to use current measurement breaker
check.
1.
Set
GlobalBaseSel
to
1
The settings are made in primary values. These values are given in the base settings
in Global base 1.
2.
Set
FunctionMode
to
Current
3.
Set
BuTripMode
to
1 out of 4
In the current measurement the three-phase currents out on the line is used. It is also
possible to measure the residual current (analogue input 4). The logics to detect
failure of the circuit breaker can be chosen:
1 out of 3
: at least one of the three-phase current shall be larger than the set level to
detect failure to break
1 out of 4
: at least one of the three-phase current and the residual current shall be
larger than the set level to detect failure to break
2 out of 4
: at least two of the three-phase current and the residual current shall be
larger than the set level to detect failure to break.
As the residual current protection is one of the protection functions to initiate the
breaker failure protection the setting
1 out of 4
is chosen.
4.
Set
Pickup_PH
to
10 %
of
IBase
Pickup_PH
should be set lower than the smallest current to be detected by the
distance protection (
I
Min
O
p
PP
) which is set 20 % of
IBase
.
5.
Set
Pickup_N
to
10 %
of
IBase
1MRK 506 334-UUS A
Section 3
REL650 setting examples
81
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...