V
ref
=-3V
0
Operate area
3I
0
RCA
= 0º
ROA
= 80º
ANSI06000652-2-en.vsd
ANSI06000652 V2 EN
Figure 112:
Characteristic for RCADir = 0° and ROADir = 80°
DirMode
is set
Forward
or
Reverse
to set the direction of the trip function from the
directional residual current function.
All the directional protection modes have a residual current release level setting
INRelPU
which is set in % of
IBase
. This setting should be chosen smaller than or equal to the lowest
fault current to be detected.
All the directional protection modes have a residual voltage release level setting
VNRelPU
which is set in % of
VBase
. This setting should be chosen smaller than or equal to the
lowest fault residual voltage to be detected.
tDef
is the definite time delay, given in s, for the directional residual current protection if
definite time delay is chosen.
The characteristic angle of the directional functions
RCADir
is set in degrees.
RCADir
is
normally set equal to 0° in a high impedance grounded network with a neutral point
resistor as the active current component is appearing out on the faulted feeder only.
RCADir
is set equal to -90° in an isolated network as all currents are mainly capacitive.
The relay open angle
ROADir
is set in degrees. For angles differing more than
ROADir
from
RCADir
the function from the protection is blocked. The setting can be used to
prevent unwanted function for non-faulted feeders, with large capacitive ground-fault
current contributions, due to CT phase angle error.
Section 7
1MRK 506 334-UUS A
Current protection
222
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...