max
1.2
t
sc
high
I
k I
³
× ×
EQUATION1265 V1 EN
(Equation 109)
where:
1.2
is a safety factor
k
t
is a factor that takes care of the transient overreach due to the DC component of the fault current and
can be considered to be less than 1.1
Iscmax is the largest fault current at a fault at the most remote point of the primary protection zone.
The operate times of the phase overcurrent protection has to be chosen so that the fault
time is so short that protected equipment will not be destroyed due to thermal overload, at
the same time as selectivity is assured. For overcurrent protection, in a radial fed network,
the time setting can be chosen in a graphical way. This is mostly used in the case of inverse
time overcurrent protection. Figure
shows how the time-versus-current curves are
plotted in a diagram. The time setting is chosen to get the shortest fault time with
maintained selectivity. Selectivity is assured if the time difference between the curves is
larger than a critical time difference.
Section 7
1MRK 506 334-UUS A
Current protection
186
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...