2
min
V
Zload
S
=
EQUATION1753-ANSI V1 EN
(Equation 69)
Where:
V
is the minimum phase-to-phase voltage in kV
S
is the maximum apparent power in MVA.
The load angle
LdAngle
can be derived according to equation
:
max
cos
max
P
LdAngle a
S
æ
ö
=
ç
÷
è
ø
EQUATION1623-ANSI V1 EN
(Equation 70)
where:
Pmax
is the maximal active power transfer during emergency conditions and
Smax
is the maximal apparent power transfer during emergency conditions.
The
RLd
can be calculated according to equation
:
cos(
)
RLd
ZLoad
LdAngle
=
×
EQUATION1624-ANSI V1 EN
(Equation 71)
The setting of
RLd
and
LdAngle
is by default set to 80 ohm/phase and 20 degrees. Those
values must be adapted to the specific application.
6.4
Additional distance protection directional function for
ground faults ZDARDIR (21D)
6.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Additional distance protection
directional function for ground faults
ZDARDIR
S00346 V1 EN
21D
1MRK 506 334-UUS A
Section 6
Impedance protection
149
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...