but the breaker is still not closed. This is done by setting parameter
AutoCont
=
Enabled
and
tAutoContWait
to the required delay for the function to proceed without a new start.
11.3.2.19
Thermal overload protection holding the auto-reclosing function back
If the input THOLHOLD (thermal overload protection holding reclosing back) is
activated, it will keep the reclosing function on a hold until it is reset. There may thus be
a considerable delay between start of Auto-Reclosing and reclosing command to the
circuit-breaker. An external logic limiting the time and sending an inhibit to the INHIBIT
input can be used. The input can also be used to set the Auto- Reclosing on hold for a
longer or shorter period.
11.3.3
Setting guidelines
11.3.3.1
Configuration
Use the PCM600 configuration tool to configure signals.
Autorecloser for 1/3-phase operation function parameters are set via the local HMI or
Parameter Setting Tool (PST). Parameter Setting Tool is a part of PCM600.
11.3.3.2
Recommendations for input signals
Please see examples in figure
. The figure is also valid for output signals.
Section 11
1MRK 506 334-UUS A
Control
328
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...