3.1.5
Faulty phase identification with load encroachment for mho
FMPSPDIS
The function is based of different principles to identify the fault type. The signals from the
different fault identification algorithms are combined in selection logic.
The advanced parameters for faulty phase identification are chosen to the default setting
values.
1.
Set
IMaxLoad
to
90 %
of
IBase
1000 A
The maximum load current for identification of three phase fault is calculated as:
1 2 180
0 90
3 138
.
IMaxLoad
.
kA
×
³
=
×
GUID-0BF144D9-D5AC-490D-9CF5-2C67C4352ADA V1 EN
(Equation 19)
2.
Set
RLd
to
70 Ω
The minimum apparent resistance during non-faulted conditions is calculated as:
(
)
2
2
0 9 138
0 8
85 7
180
min
ext ,max
.
V
RLd
.
.
P
×
£
×
=
=
W
GUID-AA7CA356-FAA7-4504-8BA0-C8ADDFC40C68-ANSI V1 EN
(Equation 20)
3.
Set
LdAngle
to
30º
It is normally considered that the apparent impedance during non-faulted condition
has a phase angle in the range ± 30º.
3.1.6
Calculating settings for scheme communication logic with delta
based blocking scheme signal transmit ZCPSCH (85)
The communication logic is used to assure fast fault clearance for all faults along the line,
that is also for faults outside the zone 1 reach of the distance protection. The logic for the
communication schemes requires a communication link between the distance protection
on the two line ends. The communication link alternatives are:
•
Power line carrier (PLC)
•
Microwave link (radio)
•
Optic fibre link
The following alternatives for communication scheme are possible:
1MRK 506 334-UUS A
Section 3
REL650 setting examples
57
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...