17.4.3
Setting guidelines
There are two possible ways to place the IED in the
TestMode
=
Enabled
” state. This
means that if the IED is set to normal operation (
TestMode
=
Disabled
), but the functions
are still shown being in the test mode, the input signal INPUT on the TESTMODE
function block must be activated in the configuration.
Forcing of binary output signals is only possible when the IED is in test mode.
17.5
Change lock CHNGLCK
17.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Change lock function
CHNGLCK
-
-
17.5.2
Application
Change lock function CHNGLCK is used to block further changes to the IED
configuration once the commissioning is complete. The purpose is to make it impossible
to perform inadvertent IED configuration and setting changes.
However, when activated, CHNGLCK will still allow the following actions that does not
involve reconfiguring of the IED:
•
Monitoring
•
Reading events
•
Resetting events
•
Reading disturbance data
•
Clear disturbances
•
Reset LEDs
•
Reset counters and other runtime component states
•
Control operations
•
Set system time
•
Enter and exit from test mode
•
Change of active setting group
The binary input controlling the function is defined in ACT or SMT. The CHNGLCK
function is configured using ACT.
1MRK 506 334-UUS A
Section 17
Basic IED functions
475
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...