12.1.3.5
Unblocking scheme
Set
Unblock
=
Restart
(Loss of guard signal will give both trip and alarm
Choose
NoRestart if only trip is required)
Set
tSecurity
= 0.035 s
12.1.3.6
Intertrip scheme
Set
Operation
=
Enabled
Set
SchemeType
=
Intertrip
Set
tCoord
50 ms (10 ms + maximal transmission time)
Set
tSendMin
= 0.1 s (0 s in parallel line applications)
Set
Unblock
=
Disabled
Set
tSecurity
= 0.015 s
12.2
Current reversal and WEI logic for distance protection
3-phase ZCRWPSCH (85)
12.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current reversal and WEI logic for
distance protection 3-phase
ZCRWPSCH
-
85
12.2.2
Application
12.2.2.1
Current reversal logic
If parallel lines are connected to common buses at both terminals, overreaching
permissive communication schemes can trip unselectable due to current reversal. The
unwanted tripping affects the healthy line when a fault is cleared on the parallel line. This
lack of security results in a total loss of interconnection between the two buses.
To avoid this kind of disturbances, a fault current reversal logic (transient blocking logic)
can be used.
1MRK 506 334-UUS A
Section 12
Scheme communication
399
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...