The IEC 61850 communication has always priority over binary inputs,
e.g. a block command on binary inputs will not prevent commands over
IEC 61850.
Accepted originator categories for PSTO
If the requested command is accepted due to the authority allocation control, the
respective value will change. Otherwise the attribute
blocked-by-switcing-hierarky
is set
in the
cause
signal. If the PSTO value is changed under a command, then the command is
reset.
The accepted originator categories for each PSTO value are shown in
Table 18:
Accepted originator categories for each PSTO
PermittdSourceToOperate
Originator
0 = Off
4,5,6
1 = Local
1,4,5,6
2 = Remote
2,3,4,5,6
3 = Faulty
4,5,6
4 = Not in use
1,2,3,4,5,6
5 = All
PSTO = All, then it is no priority between operator places. All operator places are allowed
to operate at the same time.
According to IEC61850 standard the
orCat
attribute in originator category are defined in
Table 19:
orCat attribute according to IEC61850
Value
Description
0
not-supported
1
bay-control
2
station-control
3
remote-control
4
automatic-bay
5
automatic-station
6
automatic-remote
7
maintenance
8
process
Section 11
1MRK 506 334-UUS A
Control
338
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...