![ABB REL650 series Applications Manual Download Page 369](http://html1.mh-extra.com/html/abb/rel650-series/rel650-series_applications-manual_3479164369.webp)
For a bus-section disconnector, these conditions from the B1 busbar section are valid:
en04000496_ansi.vsd
289OPTR (22089OTR)(bay 1/sect.B1)
S1DC_OP
VPS1_DC
EXDU_BB
289OPTR (22089OTR)(bay n/sect.B1)
. . .
. . .
. . .
VP289TR (V22089TR)(bay 1/sect.B1)
VP289TR (V22089TR)(bay n/sect.B1)
EXDU_BB (bay 1/sect.B1)
EXDU_BB (bay n/sect.B1)
. . .
. . .
. . .
. . .
. . .
. . .
AND
AND
AND
ANSI04000496 V1 EN
Figure 168:
Signals from any bays in section B1 to a bus-section disconnector
For a bus-section disconnector, these conditions from the B2 busbar section are valid:
en04000497_ansi.vsd
289OPTR (22089OTR)(bay 1/sect.B2)
S2DC_OP
VPS2_DC
EXDU_BB
289OPTR (22089OTR)(bay n/sect.B2)
. . .
. . .
. . .
VP289TR(V22089TR) (bay 1/sect.B2)
VP289TR(V22089TR) (bay n/sect.B2)
VPDCTR (B2/B3)
EXDU_BB (bay n/sect.B2)
. . .
. . .
. . .
. . .
. . .
. . .
AND
DCOPTR (B2/B3)
EXDU_BB (bay 1/sect.B2)
EXDU_DC (B2/B3)
AND
AND
ANSI04000497 V1 EN
Figure 169:
Signals from any bays in section B2 to a bus-section disconnector
1MRK 506 334-UUS A
Section 11
Control
363
Application manual