capacitance between the phase conductors and ground and the impedance of equipment
connected between the transformer neutral point and ground. In this network a Petersen
coil parallel with a neutral point resistor is connected to the transformer neutral. The active
ground fault current, that is, the residual current in phase with the residual voltage, is used
for line fault detection. The active residual current only flows on the connection from the
neutral point resistor and the fault point on the faulted line.
1.
Set
OpModeSel
to
3I0Cosfi
if the current component is related to the set
characteristic angle relative to the reference voltage, or
3I03V0Cosfi
if the power
component is related to the set characteristic angle relative to the reference voltage,
or
3I0 and fi,
if measuring the total residual current if the angle fi is within the set
range.
The active ground fault current, out on the faulted feeder, can be calculated by first
to calculate the residual voltage at required sensitivity (fault resistance).
0
3
1
Phase
o
f
V
V
R
Z
=
×
+
GUID-28E30403-2324-4F8E-BC5F-0FCA0D974410 V1 EN
(Equation 26)
where
(
)
0
9
3
3
3
3
3
N
N
C
c
n
n
N
C
N
N
C
R X X
Z
jX / / R / / j X
X X
j R
X
X
= -
=
+
×
-
GUID-B1001899-6E4B-4BE6-9C55-0800F736D37C V1 EN
(Equation 27)
The active ground fault current component can now be calculated according to
0
j,active
Rn
Phase
V
I
I
V
=
×
GUID-759EDA57-30C1-42C7-90EC-64F8EA10B1FE V1 EN
(Equation 28)
where I
Rn
is the rated current of the neutral point resistor.
In the network the following conditions applies:
The Petersen coil is perfectly tuned: 3X
n
= X
c
The neutral point resistor provides 25 A at ground fault without resistance. This
gives the value of R
n
.
13800
3
3187
25
n
/
R
=
=
W
GUID-6F86369A-425B-4597-A4FB-1DC0B0D13D3D V1 EN
(Equation 29)
The zero sequence network impedance works out as:
(
)
0
9
3
3
3
9561
3
3
3
N
N
C
c
n
n
n
N
C
N
N
C
R X X
Z
jX / / R / / j X
R
X X
j R
X
X
= -
=
=
=
W
+
×
-
GUID-254283ED-CBD6-4BE7-839B-192065CF0815 V1 EN
(Equation 30)
Section 3
1MRK 506 334-UUS A
REL650 setting examples
86
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...