18.1.5
General current transformer requirements
The current transformer ratio is mainly selected based on power system data for example,
maximum load. However, it should be verified that the current to the protection is higher
than the minimum operating value for all faults that are to be detected with the selected CT
ratio. The minimum operating current is different for different functions and normally
settable so each function should be checked.
The current error of the current transformer can limit the possibility to use a very sensitive
setting of a sensitive residual overcurrent protection. If a very sensitive setting of this
function will be used it is recommended that the current transformer should have an
accuracy class which have an current error at rated primary current that is less than ±1%
(for example, 5P). If current transformers with less accuracy are used it is advisable to
check the actual unwanted residual current during the commissioning.
18.1.6
Rated equivalent secondary e.m.f. requirements
With regard to saturation of the current transformer all current transformers of high
remanence and low remanence type that fulfill the requirements on the rated equivalent
limiting secondary e.m.f. E
al
below can be used. The characteristic of the non remanence
type CT (TPZ) is not well defined as far as the phase angle error is concerned. If no explicit
recommendation is given for a specific function we therefore recommend contacting ABB
to confirm that the non remanence type can be used.
The CT requirements for the different functions below are specified as a rated equivalent
limiting secondary e.m.f. E
al
according to the IEC 61869-2 standard. Requirements for
CTs specified according to other classes and standards are given at the end of this section.
18.1.6.1
Distance protection
The current transformers must have a rated equivalent secondary e.m.f. E
al
that is larger
than the maximum of the required secondary e.m.f. E
alreq
below:
s n
R
a l
a lre q
CT
L
2
pn
n
k ma x
I
I
S
E
E
R
R
I
I
³
=
×
+
+
æ
ö
×
ç
÷
è
ø
EQUATION1675 V1 EN
(Equation 178)
s n
R
a l
a lre q
CT
L
2
pn
n
kzone1
I
I
S
E
E
R
R
I
I
³
=
×
+
+
æ
ö
×
ç
÷
è
ø
EQUATION1676 V1 EN
(Equation 179)
Section 18
1MRK 506 334-UUS A
Requirements
492
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...