![ABB REL650 series Applications Manual Download Page 386](http://html1.mh-extra.com/html/abb/rel650-series/rel650-series_applications-manual_3479164386.webp)
Signal
BC12CLTR
A bus-coupler connection through the own bus-coupler exists between busbar WA1
and WA2.
BC17OPTR
No bus-coupler connection through the own bus-coupler between busbar WA1 and
WA7.
BC17CLTR
A bus-coupler connection through the own bus-coupler exists between busbar WA1
and WA7.
BC27OPTR
No bus-coupler connection through the own bus-coupler between busbar WA2 and
WA7.
BC27CLTR
A bus-coupler connection through the own bus-coupler exists between busbar WA2
and WA7.
VPBC12TR
The switch status of BC_12 is valid.
VPBC17TR
The switch status of BC_17 is valid.
VPBC27TR
The switch status of BC_27 is valid.
EXDU_BC
No transmission error from the bay that contains the above information.
These signals from each bus-section disconnector bay (A1A2_DC) are also needed. For
B1B2_DC, corresponding signals from busbar B are used. The same type of module
(A1A2_DC) is used for different busbars, that is, for both bus-section disconnector
A1A2_DC and B1B2_DC.
Signal
DCOPTR
The bus-section disconnector is open.
DCCLTR
The bus-section disconnector is closed.
VPDCTR
The switch status of bus-section disconnector DC is valid.
EXDU_DC
No transmission error from the bay that contains the above information.
If the busbar is divided by bus-section circuit breakers, the signals from the bus-section
coupler bay (A1A2_BS), rather than the bus-section disconnector bay (A1A2_DC) must
be used. For B1B2_BS, corresponding signals from busbar B are used. The same type of
module (A1A2_BS) is used for different busbars, that is, for both bus-section circuit
breakers A1A2_BS and B1B2_BS.
Signal
S1S2OPTR
No bus-section coupler connection between bus-sections 1 and 2.
S1S2CLTR
A bus-section coupler connection exists between bus-sections 1 and 2.
VPS1S2TR
The switch status of bus-section coupler BS is valid.
EXDU_BS
No transmission error from the bay that contains the above information.
For a line bay in section 1, these conditions are valid:
Section 11
1MRK 506 334-UUS A
Control
380
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...