11.5
Interlocking
11.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logical node for interlocking
SCILO
-
3
Interlocking for busbar grounding switch BB_ES
-
3
Interlocking for bus-section breaker
A1A2_BS
-
3
Interlocking for bus-section
disconnector
A1A2_DC
-
3
Interlocking for bus-coupler bay
ABC_BC
-
3
Interlocking for 1 1/2 breaker diameter
BH_CONN
-
3
Interlocking for 1 1/2 breaker diameter
BH_LINE_A
-
3
Interlocking for 1 1/2 breaker diameter
BH_LINE_B
-
3
Interlocking for double CB bay
DB_BUS_A
-
3
Interlocking for double CB bay
DB_BUS_B
-
3
Interlocking for double CB bay
DB_LINE
-
3
Interlocking for line bay
ABC_LINE
-
3
Interlocking for transformer bay
AB_TRAFO
-
3
11.5.2
Application
The main purpose of switchgear interlocking is:
•
To avoid the dangerous or damaging operation of switchgear
•
To enforce restrictions on the operation of the substation for other reasons for
example, load configuration. Examples of the latter are to limit the number of parallel
transformers to a maximum of two or to ensure that energizing is always from one
side, for example, the high voltage side of a transformer.
This section only deals with the first point, and only with restrictions caused by switching
devices other than the one to be controlled. This means that switch interlock, because of
device alarms, is not included in this section.
Disconnectors and grounding switches have a limited switching capacity. Disconnectors
may therefore only operate:
Section 11
1MRK 506 334-UUS A
Control
346
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...