18.1.6.5
Directional phase and residual overcurrent protection
If the directional overcurrent function is used the CTs must have a rated equivalent
secondary e.m.f. E
al
that is larger than or equal to the required equivalent secondary e.m.f.
E
alreq
below:
s n
R
a l
a lre q
CT
L
2
pn
n
k ma x
I
S
E
E
I
R
R
I
I
³
=
×
+
+
æ
ö
×
ç
÷
è
ø
EQUATION1681 V1 EN
(Equation 184)
where:
I
kmax
Maximum primary fundamental frequency current for close-in forward and reverse faults (A)
I
pn
The rated primary CT current (A)
I
sn
The rated secondary CT current (A)
I
n
The rated current of the protection IED (A)
R
CT
The secondary resistance of the CT (
W
)
R
L
The resistance of the secondary cable and additional load (
W
). The loop resistance containing the
phase and neutral wires, must be used for faults in solidly grounded systems. The resistance of a
single secondary wire should be used for faults in high impedance grounded systems.
S
R
The burden of an IED current input channel (VA). S
r
=0.010 VA/channel for I
r
=1 A and S
r
=0.250 VA/
channel for I
r
=5 A
18.1.7
Current transformer requirements for CTs according to other
standards
All kinds of conventional magnetic core CTs are possible to use with the IEDs if they
fulfill the requirements corresponding to the above specified expressed as the rated
equivalent limiting secondary e.m.f. E
al
according to the IEC 61869-2 standard. From
different standards and available data for relaying applications it is possible to
approximately calculate a secondary e.m.f. of the CT comparable with E
al
. By comparing
this with the required rated equivalent limiting secondary e.m.f. E
alreq
it is possible to
judge if the CT fulfills the requirements. The requirements according to some other
standards are specified below.
18.1.7.1
Current transformers according to IEC 61869-2, class P, PR
A CT according to IEC 61869-2 is specified by the secondary limiting e.m.f. E
alf
. The
value of the E
alf
is approximately equal to the corresponding E
al
. Therefore, the CTs
Section 18
1MRK 506 334-UUS A
Requirements
496
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...