Default value
5.
Set
UVPickup
to
70 %
of
VBase
Default value that must be lower than the voltage at normal operation
6.
Set
tDuration
to
0.020 s
Default value for time delay of UI detection
7.
Set
tSOTF
to
1.0 s
Default value for drop off delay of SOTF function
8.
Set
tDLD
to
0.2 s
Default value for drop off delay of Dead Line Detection
The switch onto fault logic is aimed to give fast trip of faults energized by switching
in of the line circuit breaker. There are two different modes for operation:
•
Impedance
: meaning that ZCVPSOF is released by a non-directional start
signal from the distance protection function (normally zone 2).
•
VILevel
: meaning that ZCVPSOF is released by a combination of low voltage
(lower than setting
UVPickup
) and current higher than a set value (
IphPickup
).
It is possible to set the mode of operation to the combination:
Impedance
and
VILevel
.
The function can be initiated by a binary input signal BC: (closing of the circuit
breaker). If this signal is not available there can be an automatic initiation based on
the voltage and current measurement.
3.1.9
Calculating settings for four step phase overcurrent protection
3-phase output OC4PTOC 51_67
The phase overcurrent protection is more difficult to set as the short circuit current is
highly dependent of the switching state in the power system as well as of the fault type. In
order to achieve setting that assure selective fault clearance a large number of calculations
have to be made with different fault locations, different switching states in the system and
different fault types. Below one example of setting of phase overcurrent protection for a
line in a meshed solidly grounded system is given.
The phase overcurrent protection has the following purpose:
•
Backup protection for short circuits on the line in case the distance protection is
unavailable (after fuse failure blocking)
•
Backup protection for short circuits on the adjacent busbar in case the distance
protection is unavailable (after fuse failure blocking)
•
Backup protection for short circuits on the local busbar
•
Protection for short circuits between the line circuit breaker and the line current
transformer
Section 3
1MRK 506 334-UUS A
REL650 setting examples
66
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...