16.6
Setting guidelines
The redundant station bus communication is configured using the local HMI,
Main
Menu/Configuration/Communication/TCP-IP configuation/ETHLAN1_AB
The settings can be viewed and
OperationMode
can be set in the Parameter Setting tool in
PCM600 under
IED Configuration/Communication/TCP-IP configuration/
ETHLAN1_AB
where
OperationMode
can be set to
Off
,
NonRedundant(A)
or
PRP(A+B)
. The redundant
communication will be activated when this parameter is set to
PRP(A+B).
The
ETHLAN1_AB
in the Parameter Setting tool is relevant only when the COM03
module is present.
IEC13000009-1-en.vsd
IEC13000009 V1 EN
Figure 221:
PRP1 Configured in the Parameter Setting tool
IEC13000010-1-en.vsd
IEC13000010 V1 EN
Figure 222:
Lock/Unlock parameter
1MRK 506 334-UUS A
Section 16
Station communication
467
Application manual