The fault current fed to the protection shall be calculated for the fault points 3, 4, 5
and 6 (faults about 80 % out on the adjacent lines connected to the local and remote
busbar).
The fault at point 3 is calculated with minimum source impedance at substation A
and with one line out from substation B taken out of service. This results in the
current
I
fault3,max.
= 1.56 kA
.
The fault at point 4 is calculated with minimum source impedance at substation A
and with one line out from substation B taken out of service. This gives the current
I
fault4,max.
= 1.4 kA
.
The fault at point 5 is calculated with minimum source impedance at substation B
and with one line out from substation A taken out of service. This gives the current
I
fault5,max.
= 1.56 kA
The fault at point 6 is calculated with minimum source impedance at substation B
and with one line out from substation A taken out of service. This gives the current
I
fault6,max.
= 1.35 kA
.
The current setting of step 2 is, if possible, chosen as:
1.2 · max(I
fault3,4,5,6max
) ≤ I
step2
≤ 0.7 · min(I
AB,min
, I
BA,min
)
1.2 · 1.56 ≤ I
step2
≤ 0.7 · 2.50 or 1.9 ≤ I
step2
≤ 1.75
In this case, it is not possible to fulfil the requirement above. Priority is given to
selectivity, choosing setting 1900 A and accepting a small risk that short circuits
close to the remote busbar are not tripped. This is acceptable as the distance
protection normally gives sufficient coverage of the whole line and remote busbar
from zone 2.
Setting:
Pickup2= 190 %
of
IBase
which corresponds to
1 900 A
.
2.
Set
t2
to
0.4 s
If possible the delay of step 2 should be set equal to the distance protection zone 2
(normally 0.4 s). To assure selectivity with this time delay the function should not
overreach adjacent lines out from the remote busbar and out from the local busbar.
3.1.9.4
Calculating settings for step 3
1.
Set
Pickup3
to
110 %
of
IBase
To assure that step 3 detects all short circuits on the adjacent lines out from the
remote busbar a phase-phase short circuit is applied at fault points 7 and 8. The
1MRK 506 334-UUS A
Section 3
REL650 setting examples
69
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...